Fire Alarms
When a fire-sensing device activates in your building, it sends fire alarm signals to our ULC-listed SRC. Upon receiving a fire alarm signal, FMC is obligated to notify the fire department within 30 seconds without verification.
Fire Trouble
Fire trouble indicates an issue with the fire alarm system as a whole or its components. The ULC-S561 fire monitoring standard says that FMC has five minutes to notify keyholders of a trouble condition.
Fire Supervisory
A fire supervisory alarm typically indicates an issue with something connected to your fire alarm system. For instance, if your building has a sprinkler system in addition to a fire alarm system, it will provide supervisory contacts, indicating an issue with the sprinkler system. Similarly, generators or carbon monoxide systems can also generate supervisory signals if connected to the building fire alarm system.
Sprinkler Systems
When monitoring a sprinkler system directly, without an on-site fire alarm panel, FMC will monitor similar, but different types of alarms. The monitoring system will actively monitor three common alarms, including water flow, low water pressure, and gate valve switches.
Waterflow
A water flow signal indicates that water is flowing through the sprinkler system and necessitates dispatching the fire department. FMC is required to notify the fire department of a water flow alarm signal within 30 seconds without verification.
Low-Pressure
A low-pressure signal indicates that the pressure in the sprinkler system has decreased to the point that it may not operate properly. If this signal is received, FMC will dispatch keyholders.
Gate Valve
Some valves allow water to pass into your sprinkler system. A closed gate valve means that your sprinkler system may not work, and we’ll dispatch keyholders as required by the ULC-S561 fire monitoring standard.